Caution when using EX(FUN48) or DB(FUN49) in EMII Series
When you use EX(FUN48) or DB(FUN49) in EM-II programming, see below carefully.
1. Caution
In old CPU version, EX(FUN48) and DB(FUN49) instructions work in spite of input condition (ON/OFF) by system software bug. In new CPU version, EX(FUN48) and DB(FUN49) instructions work when input condition is ON, and these don't work when input condition is OFF.
2. Example
Fig.1 shows user program on CPU memory. In old CPU version, this program works according to Fig2. In new CPU version, this program works according to Fig1.
Fig 1: User Program on Memory
![]()
![]()

![]()
Fig 2:Actual Action of EMII Old Version

3. How to distinguish You can distinguish between old version and new version by looking at manufacturing number on CPU connector. Relation between manufacturing number and CPU version shows below.
Table 1 Manufacturing number and CPU version

![]()
![]()
: Doesn't Matter
![]()
: Doesn't Matter