* 4 line x 20 Character LCD |
The EH-TD10 fulfills the need for a powerful yet cost effective operator interface system in areas where space and cost must be small. Display is a four line backlit LCD. Each line can contain up to 20 characters. Each page can contain up to 32 lines, which can be accessed by scrolling with the arrow keys. Brightness control is provided to adjust the display for easy viewing under nearly any condition.
Display Variables
PLC internal variables can be shown on any of the many display
pages (limited only by memory size). The number of variables that can be viewed
at one time is limited only by the display size. UniOP also provides scaling
(linear conversion) of the displayed data. The final value can then be shown
in several useful formats including date, time, decimal, bit, hexadecimal,
floating point, and string. Data entry with valid range verification is also
available for each data type.
Data Entry
The integral keypad on the EH-TD10 series offers 19 programmable
keys and 9 user LEDs. Slide-in legends make it easy to customize and document
the operation of the numeric keys and the user LEDs.
Security
An eight-level password protection scheme protects critical
system features from undesired access.
Alarms
The integral keypad on the EH-TD10 series offers 19 programmable
keys and 9 user LEDs. Slide-in legends make it easy to customize and document
the operation of the numeric keys and the user LEDs.
Adaptability
Custom display screens are developed using the UniOP Designer™
for Windows™ programming software. Your completed project file can be
downloaded to the display through the serial port and permanently stored in
Flash EPROM.
Keyboard Macro Editor
A feature that allows you to configure your UniOP Keys to do
a variety of functions locally in the UniOP. For example: turning pages, setting
attributes, setting LEDs, writing to the PLC, going to the event list, uploading
or downloading a recipe set and many more. This can save many hours of ladder
logic programming.
Recipes
This feature allows you to create a recipe with up to 255 parameter
sets for each page of the project file. UniOP has a total of 16K reserved
for recipe storage. You can upload or download a parameter set from or to
the PLC. Once a parameter set has been downloaded to the PLC, the data contained
within the parameter set can be modified.
UniNET Network
The UniNET network allows you to design networks of varying configurations; from two panels with one PLC to multiple panels with multiple PLCs. Data can be written to or retrieved from the PLCs in many different locations at one time. The UniNET network creates a bridge between UniOp panels which allows data to be shared by all PLCs in the network, regardless of the type or manufacturer.
* NEMA 4/12 compliant enclosure
* CE approved
* UniNET network capabilities
* Keyboard Macro Editor
* Recipe configuration
* One RS-232 / RS-422 / RS-485 / 20mA current loop serial port, speeds up
to 38,400 baud for direct PLC connection
* One RS -232 port for PC or printer communications
* One auxiliary port for high speed bus network communications
* 19 programmable keys
* 128 KB internal memory standard Flash EPROM
* Unlimited number of variables per page
* 1024 prioritized alarms
* Historical event list (last 256 events)
* Eight-level password protection
* Print reports, alarm list, and event list to serial printer
* Displays ASCII standard character set
* Real time clock with battery back-up
Top
Physical Dimensions
Cutout Width and Height Schematic
Cutout Depth 79mm (3.11")
Front Panel Thickness (max.) 8 mm (0.31")
Face-plate Height 98 mm (3.85")
Face-plate Width 195 mm (7.68")
Weight 0.9kg (2.0 lb)
Environment
Operating Temperature 0 to 50o C (32 to 122o F)
Humidity 0 to 95% RH (non-condensing)
Power Requirements 250 mA maximum, 24 VDC
Display
Type Liquid Crystal
Size 4 lines x 20 characters/line
Character height 5.15mm (approx. 13/64 inch)
Keypad
Technology Tactile feedback ( tested 5M times )
Warranty
All products are warranted for one year against defects in material and workmanship.
They may be returned in good condition within thirty days for a full refund.